State SIP for Sulfur Dioxide emissions for sulfuric acid plants
http://www.deq.louisiana.gov/portal/portals/0/planning/regs/pdf/AQ360pro.pdf
for VOC emission for nitric acid plants
http://www.deq.louisiana.gov/portal/portals/0/planning/regs/pdf/AQ363pro.pdf
for NOx emissions for non-attainment area of Baton Rouge
http://www.deq.louisiana.gov/portal/portals/0/planning/regs/pdf/AQ364pro.pdf
Often times the obnoxious odors and disturbing noise is attributed to shutdown and startup procedures. This rule will repeal the exemption set forth in LAC 33:III.2201.C.8 and replace it with provisions allowing the owner/operator of an affected point source to comply either with the emission factors imposed by LAC 33:III.2201.D at all times (including periods of startup and shutdown) or with newly-established work practice standards designed to minimize emissions during periods of startup and shutdown.
These improvements should improve air quality especially in fence line communities and in areas designated as non-attainment. The EPA's actions are largely a result of work by the Sierra Club and by public comments from across the nation, as documented in EPA's docket folder EPA-HQ-OAR-2012-0322
Proposed/June 20, 2016
|
AQ364
|
a.The owner or operator shall
operate and maintain each affected point
source, including any associated air pollution control equipment and monitoring
equipment, in a manner consistent with safety and good air pollution control
practices for minimizing emissions.
b.Effective November 22, 2016,
coal-fired and fuel oil-fired electric power
generating system boilers and fuel oil-fired stationary gas turbines shall use
natural gas during start-up. Start-up ends when any of the steam from the
boiler or steam turbine is used to generate electricity for sale over the grid,
or for any other purpose (including on-site use). If another fuel must be used
to support the shutdown process, natural gas shall be utilized.
c.Engage control devices such
as selective catalytic reduction (SCR) or
selective non-catalytic reduction (SNCR) as expeditiously as possible,
considering safety and manufacturer recommendations.
d.Minimize the start-up time of stationary internal combustion
engines to a period needed for the appropriate and safe loading of the engine,
not to exceed 30 minutes.
e.Maintain records of the
calendar date, time, and duration of each start-up
and shutdown.
f.Maintain records of the
type(s) and amount(s) of fuels used during each start-up and shutdown.